Investigation of circuit breaker arc properties in the vicinity of current-zero
ORAL
Abstract
In high voltage circuit breakers, the current is interrupted by drawing an arc between two contacts that is axially blown by a high pressure gas flow. The properties of this blown arc and its interaction with the flow immediately before a zero-crossing of the alternating current (current-zero) play an important role in determining if current interruption will be successful. A simple test device designed to represent the key features of a circuit breaker while allowing easy access for measurements was used to investigate a high current arc blown with synthetic air before current-zero. Transparent nozzles were used to permit optical investigations; the nozzles were equipped with pressure sensors to provide information about the flow conditions. The current immediately before the zero-crossing was measured with high resolution using a post-arc current measurement system. The electric field distribution in the arc was measured using a resistively coupled probe. Optical images and measurements of the arc voltage and current prior to zero-crossings of the current were compared to investigate the behavior of the arc immediately before successful and unsuccessful interruption attempts.
–
Authors
-
Patrick Stoller
ABB Switzerland Ltd
-
Martin Seeger
ABB Switzerland Ltd
-
Arthouros Iordanidis
ABB Switzerland Ltd
-
Daniel Over
ABB Switzerland Ltd
-
Bernardo Galletti
ABB Switzerland Ltd